AEC definitions

What Is a Lighting Plan?

Last reviewed: November 2026

A lighting plan is the electrical floor plan that shows every luminaire, its fixture type tag, the switches and occupancy sensors that control it, and the circuit that feeds it. Fixture tags point to the luminaire schedule, and the layout has to meet the light levels for each space, the energy code's lighting power and control requirements, and the egress lighting rules.

1234567ABCOFFICE401OFFICE402OFFICE403OFFICE404OFFICE405OFFICE406OFFICE407CONFERENCE408OPEN OFFICE409CONFERENCE410CONFERENCE411CONFERENCE412STAIRS2$a$a$a$a$a$a$a$a$a$a$a$aEXIT27'-3"27'-0"27'-3"27'-3"27'-0"27'-3"94'-8"1ALIGHTING PLANSCALE: 1/8" = 1'-0"N1234CONSULTING ENGINEERSREVISIONSPROJECTHARBOR POINT OFFICESSCALE1/8" = 1'-0"DATE04/18/2026KEY PLANSHEET TITLELIGHTING PLANSHEET NUMBERE-201

What you're looking at

Lighting Plan, annotated

A lighting plan with fixtures laid out room by room, switching, and circuit home runs.

  1. 12x4 LED troffer from the fixture schedule
  2. 2Switching zone shared by the fixtures
  3. 3Wall switch at the door
  4. 4Corridor downlights and exit sign
Sheet series
E-100 plans, separate from the power plans
Shows
Luminaires, type tags, switching, sensors, circuits, exit signs
Type tags point to
The luminaire schedule
Coordinated with
The architectural reflected ceiling plan
Energy limits
ASHRAE 90.1 Section 9 or IECC Section C405
Egress lighting
IBC Section 1008 and NFPA 101 Section 7.9

Definition

Lighting plan

Lighting plans sit in the electrical set, usually as E-100 series sheets separate from power, and they track the architect's reflected ceiling plan closely. The architect locates fixtures for the ceiling design, and the electrical engineer confirms the layout delivers the target light levels, circuits it, and assigns controls. Switch legs are marked with lowercase letters, so every fixture tagged b turns on with switch b, and emergency fixtures are marked so the inverter, battery, or generator source is clear.

In depth

Fixture tags carry the specification

A tag such as A1 or F2 next to each luminaire points to the luminaire schedule, which lists the basis of design, source, lumens, color temperature, voltage, mounting, and driver. A fixture with no matching schedule row cannot be priced, and a schedule row with no fixtures on any plan usually means a type was deleted from the design and left behind on the schedule.

Dimming protocol belongs on the schedule too. A 0-10 volt driver, a DALI driver, and a forward-phase driver need different control wiring, so the lighting plan, the schedule, and the control narrative have to agree on which one each type uses.

Controls are most of the code review

Energy codes now dictate much of what a lighting plan shows: local control in each space, occupancy or vacancy sensors in offices, classrooms, and restrooms, automatic shutoff, and daylight-responsive controls in the daylight zones beside windows and under skylights. ASHRAE 90.1 Section 9.4.1 and IECC Section C405.2 list which space types need which functions.

On the plan, controls appear as sensor symbols, switch legs, daylight zone boundaries, and sometimes a lighting control panel or relay cabinet. A sequence of operation ties them together, and plan reviewers read the narrative against the symbols.

Lighting power density is a budget for the whole layout

The energy code caps installed lighting watts per square foot, either for the building as a whole or space by space. Fixture counts on the plan multiplied by the schedule wattages have to come in under that allowance, which is why the compliance report, often from the DOE COMcheck tool, is checked against the plan.

A value engineering swap to a cheaper fixture with a higher wattage can push a space over its allowance without anyone touching the plan, because the schedule change alone does it. Rerun the compliance report whenever a fixture type changes.

Egress lighting is a separate set of requirements

NFPA 101 Section 7.9 requires emergency lighting along the means of egress to provide an initial average of 1 foot-candle and a minimum of 0.1 foot-candle at the floor, for 90 minutes after normal power fails. The lighting plan shows which fixtures are on emergency circuits, battery packs, or a central inverter, and where exit signs go.

Fixtures fed from a generator or a central inverter belong to an emergency system under NEC Article 700, which has its own wiring separation and transfer equipment requirements. A fixture tagged as emergency but circuited to a normal panel is one of the easiest errors to miss on a crowded plan.

The ceiling plan and the lighting plan must tell one story

The architect often draws fixture locations on the RCP as ceiling design intent, then the electrical drafter brings them onto the lighting plan by xref or by tracing. When the RCP changes, a traced lighting plan drifts, leaving fixtures in a grid that moved or on top of a diffuser that was relocated.

Referencing the current architectural RCP as the background and keeping fixture blocks on electrical layers, such as the E-LITE group in the US National CAD Standard, makes a reload show the conflict instead of hiding it.

Examples

Lighting plan on a real project

  • 01

    The Level 3 open office uses type A1 linear pendants at 10 feet on center, controlled by vacancy sensors and a daylight zone along the north glass, circuited to LP-3A-2.

  • 02

    Two corridor fixtures and every exit sign are marked emergency and fed from panel EL-1 downstream of the emergency transfer switch.

  • 03

    A value engineering change swaps type C downlights for a higher wattage fixture, and the lighting power density is recalculated before the bulletin issues.

Tooling

Laying out and checking lighting plans

Nomic lays out luminaires on the reflected ceiling plan background in CAD on its own computer, tags them to your luminaire schedule, circuits and switches them, and saves the DWG on your layers and blocks. It reads cutsheets for wattage and driver type and follows how your firm has shown controls and emergency fixtures on past projects.

It checks the layout against the energy code and NFPA 101 editions you name, clouds what it drew, and flags open questions such as fixtures on the RCP with no schedule type. Lighting design judgment, control intent, and the final call stay with the lighting designer or electrical engineer, who reviews and stamps the sheet.

Best AI for lighting design

Best AI for Lighting Design in 2026

FAQ

Frequently asked questions

Every luminaire with its type tag, the switches, occupancy sensors, and daylight zones that control it, the circuits that feed it, and emergency fixtures and exit signs.

The reflected ceiling plan is an architectural drawing of the ceiling: types, heights, and every device in it. The lighting plan is the electrical drawing that circuits and controls the luminaires. Fixture locations on the two must match.

The NEC for wiring, the adopted energy code such as ASHRAE 90.1 or the IECC for lighting power and controls, and IBC Section 1008 or NFPA 101 Section 7.9 for egress and emergency lighting.

Yes. Emergency fixtures and exit signs are marked on the lighting plan with their source, such as a battery pack, an inverter, or an emergency panel fed from a generator.