Hazard classification drives everything else
NFPA 13 classifies occupancies as light hazard, ordinary hazard group 1 or 2, or extra hazard group 1 or 2, and storage follows its own commodity rules. Offices and patient rooms are typically light hazard, while mechanical rooms and parking garages are typically ordinary hazard group 1.
The classification sets the design density, the design area, and the maximum coverage per head. Standard spray sprinklers in light hazard can cover up to 225 square feet each on a hydraulically calculated system, and ordinary hazard drops that to 130, so reclassifying one storage room can add heads across the whole area.