Occupant load starts the whole calculation
Each room or area is labeled with its function, area, the occupant load factor from IBC Table 1004.5 in the 2018 and 2021 editions, and the resulting occupant load. Business areas use 150 gross square feet per occupant, unconcentrated assembly with tables and chairs uses 15 net, and concentrated assembly with chairs only uses 7 net, so calling a room a training room instead of an office changes everything downstream.
Occupant load sets the number of exits under IBC Section 1006, the required egress width under Section 1005, and the plumbing fixture count. A life safety plan that gives the occupant load without the area and factor makes the reviewer redo the math.