What Is a Life Safety Plan?

Last reviewed: November 2026

A life safety plan is an architectural floor plan that shows how a building meets the egress and fire protection requirements of the building code: occupant loads, exits and exit capacity, travel distances, fire-rated walls and doors, smoke compartments, and fire extinguisher and exit sign locations. Plan reviewers use it to check means of egress and fire separation in one place.

1234567ABCEXAM201NURSE STATION202EXAM203EXAM204EXAM205EXAM206EXAM207EXAM208PATIENT ROOM209PATIENT ROOM210PATIENT ROOM211PATIENT ROOM212PATIENT ROOM213STAIRS2TRAVEL 148'-0" < 250'-0"OL 12OL 24OL 6OL 6OL 6OL 6OL 6EXITFEC1-HOUR FIRE BARRIEREXIT ACCESS TRAVEL PATH27'-3"27'-0"27'-3"27'-3"27'-0"27'-3"94'-8"1ALIFE SAFETY PLANSCALE: 1/8" = 1'-0"N1234CONSULTING ENGINEERSREVISIONSPROJECTNORTHGATE MEDICALSCALE1/8" = 1'-0"DATE04/12/2026KEY PLANSHEET TITLELIFE SAFETY PLANSHEET NUMBERG-101

What you're looking at

Life Safety Plan, annotated

A life safety plan with rated walls, occupant loads, and the exit access path checked against the travel limit.

  1. 1Rated corridor walls
  2. 2Exit access path with travel distance
  3. 3Exit sign at the stair
  4. 4Occupant load per room
Shows
Occupant loads, exits, egress paths, travel distances, rated assemblies
Governing codes
IBC Chapters 7 and 10, and NFPA 101 where adopted
Typical scale
1/16 inch to 1 foot, one floor per sheet
Sheet numbering
G or LS series, sometimes A-001
Reviewed by
The plans examiner and the fire marshal
Kept current
For the life of a healthcare facility

Definition

Life safety plan

Life safety plans are usually drawn at a small scale, often 1/16 inch to 1 foot, with a full floor on one sheet in the G or LS series, though some firms number them A-001. Many jurisdictions require one with a commercial permit submittal, and healthcare facilities keep them current for the life of the building because CMS and The Joint Commission survey against them. The plan summarizes the code strategy, and it points to the code analysis on the cover sheet, the wall types, and the door schedule for the details.

In depth

Occupant load starts the whole calculation

Each room or area is labeled with its function, area, the occupant load factor from IBC Table 1004.5 in the 2018 and 2021 editions, and the resulting occupant load. Business areas use 150 gross square feet per occupant, unconcentrated assembly with tables and chairs uses 15 net, and concentrated assembly with chairs only uses 7 net, so calling a room a training room instead of an office changes everything downstream.

Occupant load sets the number of exits under IBC Section 1006, the required egress width under Section 1005, and the plumbing fixture count. A life safety plan that gives the occupant load without the area and factor makes the reviewer redo the math.

Travel distance is drawn, not just stated

The plan traces the longest path from the most remote point to an exit, following the actual route around walls and fixed furniture, and labels its length. IBC Table 1017.2 sets the limit by occupancy and sprinkler status, such as 300 feet for a sprinklered business occupancy, and Section 1006 limits the common path of egress travel before two separate paths are available.

Exit separation is drawn too. Where two exits are required, IBC Section 1007 requires them to be separated by at least one-third of the overall diagonal of the area in a sprinklered building, or one-half without sprinklers, and the plan shows both the diagonal and the measured separation.

Rated walls, doors, and schedules have to agree

Fire barriers around exit stairs and shafts, fire partitions at corridors where required, smoke barriers, and fire walls each get a distinct line pattern and a legend with their rating. IBC Table 716.1(2) then sets the required fire protection rating of the doors in those walls.

Ratings on the life safety plan, the wall types, and the door schedule are the three a reviewer reads side by side. A 1-hour corridor on the life safety plan whose doors the door schedule lists as non-rated, instead of 20 minute doors, is a routine comment.

Healthcare adds smoke compartments

Hospitals and nursing homes are designed so patients can be defended in place, so NFPA 101 divides each floor of new healthcare occupancies into smoke compartments of no more than 22,500 square feet, with travel distance to a smoke barrier door of no more than 200 feet. The life safety plan shows each compartment and every barrier door.

Because surveyors compare existing facilities against these drawings, a renovation is expected to update the life safety plan for the whole affected floor, not only the area of work. Surveyors also look above the ceiling to confirm the smoke barriers shown on the drawing actually exist.

Devices on the plan answer the fire marshal's questions

Fire extinguishers are placed so no point is more than 75 feet of travel from a Class A extinguisher under NFPA 10 in light and ordinary hazard areas. Exit signs are placed so the way out is visible from any point in the exit access, and IBC Section 1013.1 keeps every point in an exit access corridor within 100 feet of the nearest visible sign.

Areas of refuge and other accessible means of egress under IBC Section 1009, fire department connections, standpipe locations, and the fire alarm control panel are often shown as well, so the fire marshal can check access and wayfinding on one sheet.

Examples

Life safety plan on a real project

  • 01

    A Level 1 life safety plan labels a 2,400 net square foot training room at 15 square feet per occupant for 160 occupants, which requires two exits.

  • 02

    The travel distance from the far corner of a sprinklered office floor is traced at 238 feet against the 300 foot limit for a business occupancy.

  • 03

    A hospital renovation updates smoke compartment boundaries for the whole floor and tags each barrier door with its rating.

FAQ

Frequently asked questions

An architectural floor plan that shows how a building meets egress and fire protection requirements, including occupant loads, exits, travel distances, rated walls and doors, and extinguisher and exit sign locations.

Many jurisdictions require one for commercial and multifamily permits so the plans examiner can check egress and fire separation. Requirements vary, so check the jurisdiction's submittal checklist.

A life safety plan is a construction document showing code compliance to reviewers. An evacuation plan is an operational document posted in the building to show occupants the way out. The first informs the second, but they serve different readers.

Healthcare facilities are surveyed against NFPA 101 by CMS and accrediting bodies such as The Joint Commission, and current life safety drawings showing smoke compartments and rated barriers are part of that survey.